Model Number: 6AG1334-0KE00-7AB0 6AG1314-6EH04-7AB0 6AG1313-6CG04-7AB0 6AG1331-7RD00-2AB0 6AG1322-1BF01-2XB0 Category: SIEMENS SIPLUS S7300 Product Type: PLC Type: Industry Automation Place of Origin: Made in Germany Warranty: 12 month warranty
SIPLUS S7-300 SM 334 4AI 2AQ based on 6ES7334-0KE00-0AB0 with conformal coating, -25…+70 °C, analog module isolated, 4 AI/2 AQ, 12 bit, 0-10 V for Pt100 (climatic range -120-155 degrees) and 10 kOhm measuring range, 1x 20-pole
SIPLUS S7-300 SM 334 4AI 2AQ based on 6ES7334-0KE00-0AB0 with conformal coating, -25…+70 °C, analog module isolated, 4 AI/2 AQ, 12 bit, 0-10 V for Pt100 (climatic range -120-155 degrees) and 10 kOhm measuring range, 1x 20-pole
Supply voltage | |||
Load voltage L+ | |||
● Rated value (DC) ● Reverse polarity protection |
24 V Yes |
||
Input current | |||
from supply and load voltage L+ (without load), max. | 80 mA | ||
from backplane bus 5 V DC, max. | 60 mA | ||
Power loss | |||
Power loss, typ. | 2 W | ||
Analog inputs | |||
Number of analog inputs | 4 | ||
● For voltage measurement | 2 | ||
● For resistance measurement | 4 | ||
permissible input voltage for voltage input (destruction limit), max. | 20 V; continuous; 75 V for max. 1 s (mark to space ratio 1:20) | ||
Constant measurement current for resistance-type transmitter, typ. | 490 µA; at PT100 (490 µA), at 10 kOhm (105 µa) | ||
Cycle time (all channels) max. | 85 ms | ||
Input ranges | |||
● Voltage | Yes | ||
● Current | No | ||
● Thermocouple | No | ||
● Resistance thermometer | Yes | ||
● Resistance | Yes | ||
Input ranges (rated values), voltages | |||
● 0 to +10 V — Input resistance (0 to 10 V) |
Yes 100 kΩ |
||
Input ranges (rated values), resistance thermometer | |||
● Pt 100 | Yes; only climatic range | ||
Input ranges (rated values), resistors | |||
● 0 to 10000 ohms | Yes | ||
Characteristic linearization | |||
● parameterizable — for resistance thermometer |
Yes Pt100 (climate) |
||
Cable length | |||
● shielded, max. | 100 m | ||
Analog outputs | |||
Number of analog outputs | 2 | ||
Voltage output, short-circuit protection |
Yes 10 mA |
||
Voltage output, short-circuit current, max. | |||
Output ranges, voltage | |||
● 0 to 10 V | Yes | ||
Load impedance (in rated range of output) | |||
● with voltage outputs, min. ● with voltage outputs, capacitive load, max. |
2.5 kΩ 1 µF |
||
Cable length | |||
● shielded, max. | 100 m | ||
Analog value generation for the inputs | |||
Integration and conversion time/resolution per channel | |||
● Resolution with overrange (bit including sign), max. ● Integration time, parameterizable ● Integration time (ms) ● Interference voltage suppression for interference frequency f1 in Hz |
12 bit Yes 16,67 / 20 ms 50 / 60 Hz |
||
Analog value generation for the outputs | |||
Integration and conversion time/resolution per channel | |||
● Resolution with overrange (bit including sign), max. ● Conversion time (per channel) |
12 bit 500 µs |
||
Settling time | |||
● for resistive load ● for capacitive load |
0.8 ms 0.8 ms |
||
Encoder | |||
Connection of signal encoders | |||
● for voltage measurement ● for resistance measurement with two-wire connection ● for resistance measurement with three-wire connection ● for resistance measurement with four-wire connection |
Yes Yes Yes Yes |
||
Errors/accuracies | |||
Operational error limit in overall temperature range | |||
● Voltage, relative to input range, (+/-) ● Resistance, relative to input range, (+/-) ● Resistance thermometer, relative to input range, (+/- ) ● Voltage, relative to output range, (+/-) |
0.8 %; 0 to 10V 3.7 %; 10 kOhm 1.1 % 1.1 % |
||
Basic error limit (operational limit at 25 °C) | |||
● Voltage, relative to input range, (+/-) ● Resistance, relative to input range, (+/-) ● Resistance thermometer, relative to input range, (+/- ) ● Voltage, relative to output range, (+/-) |
0.5 %; 0 to 10V 2.8 %; 10 kOhm 0.8 % 0.85 % |
||
Interrupts/diagnostics/status information | |||
Alarms | No | ||
Diagnostics function | No | ||
Potential separation | |||
Potential separation analog inputs | |||
● between the channels and backplane bus | Yes | ||
Potential separation analog outputs | |||
● between the channels ● between the channels and backplane bus ● between the channels and the power supply of the electronics |
No Yes Yes |
||
Isolation | |||
Isolation tested with | 500 V DC | ||
Standards, approvals, certificates | |||
CE mark | Yes | ||
UL approval | Yes; File E239877 | ||
RCM (formerly C-TICK) | Yes | ||
KC approval | Yes | ||
EAC (formerly Gost-R) | Yes | ||
Ambient conditions | |||
Ambient temperature during operation | |||
● min. ● max. |
-25 °C; = Tmin 70 °C; = Tmax; 60 °C @ UL/cUL, ATEX and FM use |
||
Ambient temperature during storage/transportation | |||
● min. ● max. |
-40 °C 70 °C |
||
Altitude during operation relating to sea level | |||
● Installation altitude above sea level, max. ● Ambient air temperature-barometric pressure- altitude |
5 000 m Tmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500 m) // Tmin ... (Tmax -20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5 000 m) |
||
Relative humidity | |||
● With condensation, tested in accordance with IEC 60068-2-38, max. | 100 %; RH incl. condensation/frost (no commissioning under condensation conditions) | ||
Resistance | |||
Use in stationary industrial systems | |||
— to biologically active substances according to EN 60721-3-3 — to chemically active substances according to EN 60721-3-3 — to mechanically active substances according to EN 60721-3-3 |
Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request Yes; Class 3C4 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); * Yes; Class 3S4 incl. sand, dust, * |
||
Use on ships/at sea | |||
— to biologically active substances according to EN 60721-3-6 — to chemically active substances according to EN 60721-3-6 — to mechanically active substances according to EN 60721-3-6 |
Yes; Class 6B2 mold and fungal spores (excluding fauna); Class 6B3 on request Yes; Class 6C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); * Yes; Class 6S3 incl. sand, dust; * |
||
Usage in industrial process technology | |||
— Against chemically active substances acc. to EN 60654-4 — Environmental conditions for process, measuring and control systems acc. to ANSI/ISA- 71.04 |
Yes; Class 3 (excluding trichlorethylene) Yes; Level GX group A/B (excluding trichlorethylene; harmful gas concentrations up to the limits of EN 60721-3-3 class 3C4 permissible); level LC3 (salt spray) and level LB3 (oil) |
||
Remark | |||
— Note regarding classification of environmental conditions acc. to EN 60721, EN 60654-4 and ANSI/ISA-71.04 | * The supplied plug covers must remain in place over the unused interfaces during operation! | ||
connection method / header | |||
required front connector | 20-pin | ||
Dimensions | |||
Width | 40 mm | ||
Height | 125 mm | ||
Depth | 117 mm | ||
Weights | |||
Weight, approx. | 200 g |
6AG1332-5HB01-2AB0 | 6AG1313-5BG04-7AB0 | 6AG1321-1FF10-7AA0 |
6AG1313-6CG04-2AY0 | 6AG1331-7NF00-2AB0 | 6AG1322-1BL00-2AA0 |
6AG1350-1AH03-2AE0 | 6AG1314-6CH04-7AB0 | 6AG1331-7TB00-7AB0 |
6AG1332-7ND02-4AB0 | 6AG1341-1CH02-7AE0 | 6AG1322-1FF01-7AA0 |
6AG1322-1BH01-2AA0 | 6AG1314-6CH04-2AY0 | 6AG1312-5BF04-7AB0 |
6AG1350-2AH01-4AE0 | 6AG1321-1FH00-7AA0 | 6AG1331-7SF00-4AB0 |
6AG1317-2EK14-7AB0 | 6AG1314-1AG14-7AB0 | 6AG1315-2EH14-7AB0 |
6AG1341-1AH02-7AE0 | 6AG1322-5FF00-4AB0 | 6AG1321-7RD00-4AB0 |
6AG1312-5BF04-2AY0 | 6AG1334-0KE00-7AB0 | 6AG1314-6EH04-7AB0 |
6AG1313-6CG04-7AB0 | 6AG1331-7RD00-2AB0 | 6AG1322-1BF01-2XB0 |
6AG1322-1FH00-7AA0 | 6AG1315-2EH14-2AY0 | 6AG1317-2EK14-2AY0 |
6AG1332-5HF00-2AB0 | 6AG1321-1FF01-2AA0 | 6AG1331-7PF11-4AB0 |
6AG1313-5BG04-2AY0 | 6AG1321-7BH01-4AS0 | 6AG1340-1AH02-2AE0 |
6AG1315-2AH14-7AB0 | 6AG1332-5HD01-7AB0 | 6AG1340-1CH02-2AE0 |
6AG1314-6BH04-7AB0 |