Model Number: 6AG1322-1BL00-2AA0 6AG1350-1AH03-2AE0 6AG1314-6CH04-7AB0 6AG1331-7TB00-7AB0 6AG1332-7ND02-4AB0 Category: SIEMENS SIPLUS S7300 Product Type: PLC Type: Industry Automation Place of Origin: Made in Germany Warranty: 12 month warranty
SIPLUS S7-300 SM 322 32DQ 40-pole based on 6ES7322-1BL00-0AA0 with conformal coating, -25…+70 °C, digital output isolated, 32 DQ, 24 V DC, 0.5 A, 1x 40-pole, total current 4 A/group (16 A/module)
SIPLUS S7-300 SM 322 32DQ 40-pole based on 6ES7322-1BL00-0AA0 with conformal coating, -25…+70 °C, digital output isolated, 32 DQ, 24 V DC, 0.5 A, 1x 40-pole, total current 4 A/group (16 A/module)
| Supply voltage | |
| Load voltage L+ | |
|
● Rated value (DC) ● permissible range, lower limit (DC) ● permissible range, upper limit (DC) |
24 V 20.4 V 28.8 V |
| Input current | |
| from load voltage L+ (without load), max. | 160 mA |
| from backplane bus 5 V DC, max. | 110 mA |
| Power loss | |
| Power loss, typ. | 6.6 W |
| Digital outputs | |
| Number of digital outputs | 32 |
| Short-circuit protection | Yes; Electronic |
| ● Response threshold, typ. | 1 A |
| Limitation of inductive shutdown voltage to | L+ (-53 V) |
| Controlling a digital input | Yes |
| Switching capacity of the outputs | |
| ● on lamp load, max. | 5 W |
| Load resistance range | |
|
● lower limit ● upper limit |
48 Ω 4 kΩ |
| Output voltage | |
| ● for signal "1", min. | L+ (-0.8 V) |
| Output current | |
| ● for signal "1" rated value | 0.5 A |
| ● for signal "1" permissible range for 0 to 40 °C, min. | 5 mA |
| ● for signal "1" permissible range for 0 to 40 °C, max. | 0.6 A |
| ● for signal "1" permissible range for 40 to 60 °C, min. | 5 mA |
| ● for signal "1" permissible range for 40 to 60 °C, max. | 0.6 A |
| ● for signal "1" minimum load current | 5 mA |
| ● for signal "0" residual current, max. | 0.5 mA |
| Output delay with resistive load | |
|
● "0" to "1", max. ● "1" to "0", max. |
100 µs 500 µs |
| Parallel switching of two outputs | |
|
● for uprating ● for redundant control of a load |
No Yes; only outputs of the same group |
| Switching frequency | |
|
● with resistive load, max. ● with inductive load (acc. to IEC 60947-5-1, DC13), max. ● on lamp load, max. |
100 Hz 0.5 Hz 10 Hz |
| Total current of the outputs (per group) | |
| horizontal installation | |
|
— up to 40 °C, max. — up to 60 °C, max. — up to 70 °C, max. |
4 A 3 A 2 A |
| vertical installation | |
| — up to 40 °C, max. | 2 A |
| Cable length | |
|
● shielded, max. ● unshielded, max. |
1 000 m 600 m |
| Interrupts/diagnostics/status information | |
| Alarms | No |
| Diagnostics function | No |
| Alarms | |
| ● Diagnostic alarm | No |
| Diagnoses | |
|
● Diagnostic information readable ● Wire-break ● Short-circuit ● missing load voltage |
No No No No |
| Diagnostics indication LED | |
|
● Rated load voltage PWR (green) ● Fuse OK FSG (green) ● Group error SF (red) ● Status indicator digital output (green) ● Channel fault indicator F (red) |
No No No Yes; per channel No |
| Potential separation | |
| Potential separation digital outputs | |
|
● between the channels ● between the channels, in groups of ● between the channels and backplane bus |
Yes 8 Yes; Optocoupler |
| Isolation | |
| Isolation tested with | 500 V DC |
| Standards, approvals, certificates | |
| CE mark | Yes |
| UL approval | Yes; File E239877 |
| RCM (formerly C-TICK) | Yes |
| KC approval | Yes |
| EAC (formerly Gost-R) | Yes |
| Railway application | |
| ● EN 50155 | Yes; Sections 4, 5 and 12; no further agreements apply; T1, Category 1, Class A/B, EN 50155:2007 (see SIOS entry 109755985) |
| Ambient conditions | |
| Ambient temperature during operation | |
|
● min. ● max. |
-25 °C; = Tmin 70 °C; = Tmax; for use on railway vehicles according to EN50155, the rated temperature range -25 ... +55 °C (T1) or 60 °C @ UL/ULhaz/ATEX/FM use applies |
| Ambient temperature during storage/transportation | |
|
● min. ● max. |
-40 °C 70 °C |
| Altitude during operation relating to sea level | |
|
● Installation altitude above sea level, max. ● Ambient air temperature-barometric pressure- altitude |
5 000 m Tmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500 m) // Tmin ... (Tmax -20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5 000 m) |
| Relative humidity | |
| ● With condensation, tested in accordance with IEC 60068-2-38, max. | 100 %; RH incl. condensation/frost (no commissioning under condensation conditions) |
| Resistance | |
| Use in stationary industrial systems | |
|
— to biologically active substances according to EN 60721-3-3 — to chemically active substances according to EN 60721-3-3 — to mechanically active substances according to EN 60721-3-3 |
Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request Yes; Class 3C4 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); * Yes; Class 3S4 incl. sand, dust, * |
| Use on land craft, rail vehicles and special-purpose vehicles | |
|
— to biologically active substances according to EN 60721-3-5 — to chemically active substances according to EN 60721-3-5 — to mechanically active substances according to EN 60721-3-5 |
Yes; Class 5B2 mold, fungus and dry rot spores (with the exception of fauna); Class 5B3 on request Yes; Class 5C3 (RH < 75 %) incl. salt spray acc. to EN 50155 (ST2); * Yes; Class 5S3 incl. sand, dust; * |
| Use on ships/at sea | |
|
— to biologically active substances according to EN 60721-3-6 — to chemically active substances according to EN 60721-3-6 — to mechanically active substances according to EN 60721-3-6 |
Yes; Class 6B2 mold and fungal spores (excluding fauna); Class 6B3 on request Yes; Class 6C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); * Yes; Class 6S3 incl. sand, dust; * |
| Usage in industrial process technology | |
|
— Against chemically active substances acc. to EN 60654-4 — Environmental conditions for process, measuring and control systems acc. to ANSI/ISA- 71.04 |
Yes; Class 3 (excluding trichlorethylene) Yes; Level GX group A/B (excluding trichlorethylene; harmful gas concentrations up to the limits of EN 60721-3-3 class 3C4 permissible); level LC3 (salt spray) and level LB3 (oil) |
| Remark | |
| — Note regarding classification of environmental conditions acc. to EN 60721, EN 60654-4 and ANSI/ISA-71.04 | * The supplied plug covers must remain in place over the unused interfaces during operation! |
| connection method / header | |
| required front connector | 40-pin |
| Dimensions | |
| Width | 40 mm |
| Height | 125 mm |
| Depth | 120 mm |
| Weights | |
| Weight, approx. | 260 g |
| 6AG1332-5HB01-2AB0 | 6AG1313-5BG04-7AB0 | 6AG1321-1FF10-7AA0 |
| 6AG1313-6CG04-2AY0 | 6AG1331-7NF00-2AB0 | 6AG1322-1BL00-2AA0 |
| 6AG1350-1AH03-2AE0 | 6AG1314-6CH04-7AB0 | 6AG1331-7TB00-7AB0 |
| 6AG1332-7ND02-4AB0 | 6AG1341-1CH02-7AE0 | 6AG1322-1FF01-7AA0 |
| 6AG1322-1BH01-2AA0 | 6AG1314-6CH04-2AY0 | 6AG1312-5BF04-7AB0 |
| 6AG1350-2AH01-4AE0 | 6AG1321-1FH00-7AA0 | 6AG1331-7SF00-4AB0 |
| 6AG1317-2EK14-7AB0 | 6AG1314-1AG14-7AB0 | 6AG1315-2EH14-7AB0 |
| 6AG1341-1AH02-7AE0 | 6AG1322-5FF00-4AB0 | 6AG1321-7RD00-4AB0 |
| 6AG1312-5BF04-2AY0 | 6AG1334-0KE00-7AB0 | 6AG1314-6EH04-7AB0 |
| 6AG1313-6CG04-7AB0 | 6AG1331-7RD00-2AB0 | 6AG1322-1BF01-2XB0 |
| 6AG1322-1FH00-7AA0 | 6AG1315-2EH14-2AY0 | 6AG1317-2EK14-2AY0 |
| 6AG1332-5HF00-2AB0 | 6AG1321-1FF01-2AA0 | 6AG1331-7PF11-4AB0 |
| 6AG1313-5BG04-2AY0 | 6AG1321-7BH01-4AS0 | 6AG1340-1AH02-2AE0 |
| 6AG1315-2AH14-7AB0 | 6AG1332-5HD01-7AB0 | 6AG1340-1CH02-2AE0 |
| 6AG1314-6BH04-7AB0 |