品牌:SIEMENS/西门子 系列:西门子彩色精简面板 型号:6AG1123-2DB03-2AX0 6AG1123-2GA03-2AX0 6AG1123-2GB03-2AX0
SIPLUS HMI KTP400 Basic Color PN based on 6AV2123-2DB03-0AX0 with conformal coating, -20…+60 °C, 4" TFT display, 65536 colors PROFINET interface
| General information | |
| Product type designation | KTP400 Basic color PN |
| Display | |
| Design of display | TFT widescreen display, LED backlighting |
| Screen diagonal | 4.3 in |
| Display width | 95 mm |
| Display height | 53.9 mm |
| Number of colors | 65536 |
| Resolution (pixels) | |
|
● Horizontal image resolution ● Vertical image resolution |
480 pixel 272 pixel |
| Backlighting | |
|
● MTBF backlighting (at 25 °C) ● Backlight dimmable |
20 000 h Yes |
| Control elements | |
| Keyboard fonts | |
| ● Function keys | |
| — Number of function keys | 4 |
| — Number of function keys with LEDs | 0 |
| ● Keys with LED | No |
| ● System keys | No |
| ● Numeric keyboard | Yes; Onscreen keyboard |
| ● alphanumeric keyboard | Yes; Onscreen keyboard |
| Touch operation | |
| ● Design as touch screen | Yes; Analog-resistive |
| Installation type/mounting | |
| Mounting position | |
| Mounting in portrait format possible | Yes |
| Mounting in landscape format possible | Yes |
| maximum permissible angle of inclination without external | 35° |
| ventilation | |
| Supply voltage | |
| Type of supply voltage | DC |
| Rated value (DC) | 24 V |
| permissible range, lower limit (DC) | 19.2 V |
| permissible range, upper limit (DC) | 28.8 V |
| Input current | |
| Current consumption (rated value) |
125 mA 0.2 A²·s |
| Starting current inrush I²t | |
| Power | |
| Active power input, typ. | 3 W |
| Processor | |
| Processor type | ARM |
| Memory | |
| Flash | Yes |
| RAM |
Yes |
| Memory available for user data | 10 Mbyte |
| Type of output | |
|
Acoustics ● Buzzer ● Speaker |
Yes No |
| Time of day | |
| Clock | |
|
● Hardware clock (real-time) ● Software clock ● retentive ● synchronizable |
Yes Yes Yes Yes |
| Interfaces | |
| Number of industrial Ethernet interfaces |
1 0
0 0 1; Up to 16 GB 0 0 0 0 No |
| Number of RS 485 interfaces | |
| Number of RS 422 interfaces | |
| Number of RS 232 interfaces | |
| Number of USB interfaces | |
| Number of 20 mA interfaces (TTY) | |
| Number of parallel interfaces | |
| Number of other interfaces | |
| Number of SD card slots | |
| With software interfaces | |
| Industrial Ethernet | |
| ● Industrial Ethernet status LED | 2 |
| Protocols | |
| PROFINET |
Yes No No No Yes No |
| Supports protocol for PROFINET IO | |
| IRT | |
| PROFIBUS | |
| EtherNet/IP | |
| MPI | |
| Protocols (Ethernet) | |
|
● TCP/IP ● DHCP ● SNMP ● DCP ● LLDP |
Yes Yes Yes Yes Yes |
| WEB characteristics | |
|
● HTTP ● HTML |
No No |
| Redundancy mode | |
| Media redundancy | |
| — MRP | No |
| Further protocols | |
|
● CAN ● MODBUS |
No Yes; Modicon (MODBUS TCP/IP) |
| Interrupts/diagnostics/status information | |
| Diagnoses | |
| ● Diagnostic information readable | No |
| EMC | |
| Emission of radio interference acc. to EN 55 011 | |
| ● Limit class A, for use in industrial areas | Yes |
| ● Limit class B, for use in residential areas | No |
| Degree and class of protection | |
| IP (at the front) |
IP65 IP20 Yes Yes |
| IP (rear) | |
|
NEMA (front) ● Enclosure Type 4 at the front ● Enclosure Type 4x at the front |
|
| Standards, approvals, certificates | |
| CE mark |
Yes Yes Yes Yes |
| cULus | |
| RCM (formerly C-TICK) | |
| KC approval | |
| Use in hazardous areas | |
|
● ATEX Zone 2 ● ATEX Zone 22 ● IECEx Zone 2 ● IECEx Zone 22 ● cULus Class I Zone 1 ● cULus Class I Zone 2, Division 2 ● FM Class I Division 2 |
No No No No No No No |
| Marine approval | |
|
● Germanischer Lloyd (GL) ● American Bureau of Shipping (ABS) ● Bureau Veritas (BV) ● Det Norske Veritas (DNV) ● Lloyds Register of Shipping (LRS) ● Nippon Kaiji Kyokai (Class NK) ● Polski Rejestr Statkow (PRS) ● Chinese Classification Society (CCS) |
Yes Yes Yes Yes Yes Yes No No |
| Ambient conditions | |
| Ambient temperature during operation | |
| Operation (vertical installation) | |
|
— For vertical installation, min. — For vertical installation, max. |
0 °C 50 °C |
| Operation (max. tilt angle) | |
|
— At maximum tilt angle, min. — At maximum tilt angle, max. |
0 °C 40 °C |
| Operation (vertical installation, portrait format) | |
|
— For vertical installation, min. — For vertical installation, max. |
0 °C 40 °C |
| Operation (max. tilt angle, portrait format) | |
|
— At maximum tilt angle, min. — At maximum tilt angle, max. |
0 °C 35 °C |
| Ambient temperature during storage/transportation | |
|
● min. ● max. |
-20 °C 60 °C |
| Relative humidity | |
| ● Operation, max. | 90 %; no condensation |
| Operating systems | |
| proprietary | Yes |
| pre-installed operating system | |
| ● Windows CE | No |
| configuration / header | |
| Message indicator |
Yes Yes Yes Yes Yes |
| Alarm system (incl. buffer and acknowledgment) | |
| Process value display (output) | |
| Process value default (input) possible | |
| Recipe management | |
| Configuration software | |
|
● STEP 7 Basic (TIA Portal) ● STEP 7 Professional (TIA Portal) ● WinCC flexible Compact ● WinCC flexible Standard ● WinCC flexible Advanced ● WinCC Basic (TIA Portal) ● WinCC Comfort (TIA Portal) ● WinCC Advanced (TIA Portal) ● WinCC Professional (TIA Portal) |
Yes; via integrated WinCC Basic (TIA Portal) Yes; via integrated WinCC Basic (TIA Portal) No No No Yes Yes Yes Yes |
| Languages | |
| Online languages | |
| ● Number of online/runtime languages | 10 |
| Project languages | |
| ● Languages per project | 32 |
| Functionality under WinCC (TIA Portal) | |
| Libraries |
Yes No No No Yes No Yes Yes 500 |
|
Applications/options ● Web browser ● SIMATIC WinCC Sm@rtServer |
|
| Number of Visual Basic Scripts | |
|
Task planner ● time-controlled ● task-controlled |
|
|
Help system ● Number of characters per info text |
|
| Message system | |
|
● Number of alarm classes ● Bit messages — Number of bit messages ● Analog messages — Number of analog messages ● S7 alarm number procedure ● System messages HMI ● System event, more (SIMATIC S7, SINUMERIK, SIMOTION, ... ) ● Number of characters per message ● Number of process values per message ● Acknowledgment groups ● Message indicator ● Message buffer — Number of entries — Circulating buffer — retentive — maintenance-free |
32 1 000 25 No Yes Yes; System message buffer of the SIMATIC S7-1200 and S7-1500 80 8 Yes Yes 256 Yes Yes Yes |
| Recipe management | |
|
● Number of recipes ● Data records per recipe ● Entries per data record ● Size of internal recipe memory ● Recipe memory expandable |
50 100 100 256 kbyte No |
| Variables | |
|
● Number of variables per device ● Number of variables per screen ● Limit values ● Multiplexing ● Structures ● Arrays |
800 100 Yes Yes No Yes |
| Images | |
|
● Number of configurable images ● Permanent window/default |
250 Yes |
|
● Global image ● Pop-up images ● Slide-in images ● Image selection by PLC ● Image number in the PLC |
Yes No No Yes Yes |
| Image objects | |
|
● Number of objects per image ● Text fields ● I/O fields ● Graphic I/O fields (graphics list) ● Symbolic I/O fields (text list) ● Date/time fields ● Switches ● Buttons ● Graphic display ● Icons ● Geometric objects |
100 Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes |
| Complex image objects | |
|
● Number of complex objects per screen ● Alarm view ● Trend view ● User view ● Status/control ● Sm@rtClient view ● Recipe view ● f(x) trend view ● System diagnostics view ● Media Player ● HTML browser ● PDF display ● IP camera display ● Bar graphs ● Sliders ● Pointer instruments ● Analog/digital clock |
10 Yes Yes Yes No No Yes No Yes; System message buffer of the SIMATIC S7-1200 and S7-1500 No Yes No No Yes No No No |
| Lists | |
|
● Number of text lists per project ● Number of entries per text list ● Number of graphics lists per project ● Number of entries per graphics list |
150 100 100 100 |
| Archiving | |
|
● Number of archives per device ● Number of entries per archive ● Message archive ● Process value archive ● Archiving methods — Sequential archive — Short-term archive ● Memory location — Memory card — USB memory — Ethernet ● Data storage format — CSV — TXT — RDB |
2 10 000 Yes Yes Yes Yes No Yes No No Yes No |
| Security | |
|
● Number of user groups ● Number of user rights ● Number of users |
50 32 50 |
|
● Password export/import ● SIMATIC Logon |
Yes No |
| Character sets | |
|
● Keyboard fonts — US English |
Yes |
| Transfer (upload/download) | |
|
● MPI/PROFIBUS DP ● USB ● Ethernet ● using external storage medium |
Yes No No Yes |
| Process coupling | |
|
● S7-1200 ● S7-1500 ● S7-200 ● S7-300/400 ● LOGO! ● WinAC ● SINUMERIK ● SIMOTION ● Allen Bradley (EtherNet/IP) ● Allen Bradley (DF1) ● Mitsubishi (MC TCP/IP) ● Mitsubishi (FX) ● OMRON (FINS TCP) ● OMRON (LINK/Multilink) ● Modicon (Modbus TCP/IP) ● Modicon (Modbus) |
Yes Yes Yes Yes Yes Yes Yes;No access to NCK data Yes Yes No Yes No No No Yes No |
| Service tools/configuration aids | |
|
● Backup/Restore manually ● Backup/Restore automatically ● Simulation ● Device switchover |
Yes No Yes Yes |
| Peripherals/Options | |
| Printer |
No No No No Yes Yes Yes |
| SIMATIC HMI MM memory card: Multi Media Card | |
| SIMATIC HMI SD memory card: Secure Digital memory card | |
| SIMATIC HMI CF memory card Compact Flash Card | |
| USB memory | |
| SIMATIC IPC USB Flashdrive (USB stick) | |
| SIMATIC HMI USB stick | |
| Mechanics/material | |
|
Enclosure material (front) ● Plastic ● Aluminum ● Stainless steel |
Yes No No |
| Dimensions | |
| Width of the housing front |
141 mm |
| Height of housing front | 116 mm |
| Mounting cutout, width | 123 mm |
| Mounting cutout, height | 99 mm |
| Overall depth | 33 mm |
| Weights | |
| Weight (without packaging) | 360 g |
| Weight (with packaging) | 470 g |
| Ambient conditions | ||
| Ambient temperature during operation | ||
| Operation (vertical installation) | ||
|
— For vertical installation, min. — For vertical installation, max. |
-20 °C; = Tmin 60 °C; = Tmax |
|
| Operation (max. tilt angle) | ||
|
— At maximum tilt angle, min. — At maximum tilt angle, max. |
-20 °C; = Tmin 40 °C; = Tmax |
|
| Operation (vertical installation, portrait format) | ||
|
— For vertical installation, min. — For vertical installation, max. |
-20 °C; = Tmin 40 °C; = Tmax |
|
| Operation (max. tilt angle, portrait format) | ||
|
— At maximum tilt angle, min. — At maximum tilt angle, max. |
-20 °C; = Tmin 35 °C; = Tmax |
|
| Ambient temperature during storage/transportation | ||
|
● min. ● max. |
-20 °C 60 °C |
|
| Altitude during operation relating to sea level | ||
|
● Installation altitude above sea level, max. ● Ambient air temperature-barometric pressure- altitude |
5 000 m Tmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500 m) // Tmin ... (Tmax -20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5 000 m) |
|
| Relative humidity | ||
| ● With condensation, tested in accordance with IEC 60068-2-38, max. | 100 %; RH incl. condensation/frost (no commissioning under condensation conditions) | |
| Resistance | ||
| Coolants and lubricants | ||
| — Resistant to commercially available coolants and lubricants | Yes; Incl. diesel and oil droplets in the air | |
| Use in stationary industrial systems | ||
|
— to biologically active substances according to EN 60721-3-3 — to chemically active substances according to EN 60721-3-3 — to mechanically active substances according to EN 60721-3-3 |
Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request Yes; Class 3C4 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); * Yes; Class 3S4 incl. sand, dust, * |
|
| Use on ships/at sea | ||
|
— to biologically active substances according to EN 60721-3-6 — to chemically active substances according to EN 60721-3-6 — to mechanically active substances according to EN 60721-3-6 |
Yes; Class 6B2 mold and fungal spores (excluding fauna); Class 6B3 on request Yes; Class 6C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); * Yes; Class 6S3 incl. sand, dust; * |
|
| Usage in industrial process technology | ||
|
— Against chemically active substances acc. to EN 60654-4 — Environmental conditions for process, measuring and control systems acc. to ANSI/ISA- 71.04 |
Yes; Class 3 (excluding trichlorethylene) Yes; Level GX group A/B (excluding trichlorethylene; harmful gas concentrations up to the limits of EN 60721-3-3 class 3C4 permissible); level LC3 (salt spray) and level LB3 (oil) |
|
| Remark | ||
| — Note regarding classification of environmental conditions acc. to EN 60721, EN 60654-4 and ANSI/ISA-71.04 | * The supplied plug covers must remain in place over the unused interfaces during operation! | |
| Conformal coating | ||
|
● Coatings for printed circuit board assemblies acc. to EN 61086 ● Protection against fouling acc. to EN 60664-3 ● Military testing according to MIL-I-46058C, Amendment 7 ● Qualification and Performance of Electrical |
Yes; Class 2 for high reliability Yes; Type 1 protection Yes; Discoloration of coating possible during service life Yes; Conformal coating, Class A |
|