品牌:SIEMENS/西门子 系列:西门子SIMATIC S7-1200F紧凑型CPU 型号:6ES7215-1HF40-0XB0 6ES7215-1AF40-0XB0 6ES7211-1HE40-0XB0 6ES7212-1BE40-0XB0 6ES7212-1HE40-0XB0 工作电压:24V









SIMATIC S7-1200F, CPU 1215 FC, compact CPU, DC/DC/relay, 2 PROFINET ports, onboard I/O: 14 DI 24 V DC; 10 DO relay 2 A, 2 AI 0-10 V DC, 2 AO 0-20 mA DC, Power supply: DC 20.4-28.8 V DC, Program/data memory 150 KB
| General information | |
| Product type designation | CPU 1215FC DC/DC/DC |
| Firmware version | V4.5 |
| Engineering with | |
| ● Programming package | STEP 7 V17 or higher |
| Supply voltage | |
|
Rated value (DC) ● 24 V DC |
Yes |
| permissible range, lower limit (DC) | 20.4 V |
| permissible range, upper limit (DC) | 28.8 V |
| Reverse polarity protection | Yes |
| Load voltage L+ | |
|
● Rated value (DC) ● permissible range, lower limit (DC) ● permissible range, upper limit (DC) |
24 V 20.4 V 28.8 V |
| Input current | |
| Current consumption (rated value) |
500 mA; CPU only 1 500 mA; CPU with all expansion modules 12 A; at 28.8 V |
| Current consumption, max. | 1 500 mA; CPU with all expansion modules |
| Inrush current, max. |
12 A; at 28.8 V 12 A; at 28.8 V |
| I²t | 0.5 A²·s |
| Output current | |
| for backplane bus (5 V DC), max. | 1 600 mA; Max. 5 V DC for SM and CM |
| Encoder supply | |
| 24 V encoder supply | |
| ● 24 V | L+ minus 4 V DC min. |
| Power loss | |
| Power loss, typ. | 12 W |
| Memory | |
| Work memory | |
|
● integrated ● expandable |
125 kbyte No |
| Load memory | |
|
● integrated ● Plug-in (SIMATIC Memory Card), max. |
4 Mbyte with SIMATIC memory card |
| Backup | |
|
● present ● maintenance-free ● without battery |
Yes Yes Yes |
|
|
|
| for bit operations, typ. | 0.08 µs; / instruction |
| for word operations, typ. | 1.7 µs; / instruction |
| for floating point arithmetic, typ. | 2.3 µs; / instruction |
| CPU-blocks | |
| Number of blocks (total) | DBs, FCs, FBs, counters and timers. The maximum number of addressable blocks ranges from 1 to 65535. There is no restriction, the entire working memory can be used |
| OB | |
| ● Number, max. | Limited only by RAM for code |
| Data areas and their retentivity | |
| Retentive data area (incl. timers, counters, flags), max. | 14 kbyte |
| Flag | |
| ● Size, max. | 8 kbyte; Size of bit memory address area |
| Local data | |
| ● per priority class, max. | 16 kbyte; Priority class 1 (program cycle): 16 KB, priority class 2 to 26: 6 KB |
| Address area | |
| Process image | |
|
● Inputs, adjustable ● Outputs, adjustable |
1 kbyte 1 kbyte |
| Hardware configuration | |
| Number of modules per system, max. | 3 comm. modules, 1 signal board, 8 signal modules |
| Time of day | |
| Clock | |
|
● Hardware clock (real-time) ● Backup time ● Deviation per day, max. |
Yes 480 h; Typical ±60 s/month at 25 °C |
| Digital inputs | |
|
Number of digital inputs ● of which inputs usable for technological functions |
14; Integrated 6; HSC (High Speed Counting) |
| Source/sink input | Yes |
| Number of simultaneously controllable inputs | |
| all mounting positions | |
| — up to 40 °C, max. | 14 |
| Input voltage | |
|
● Rated value (DC) ● for signal "0" ● for signal "1" |
24 V 5 V DC at 1 mA 15 V DC at 2.5 mA |
| Input delay (for rated value of input voltage) | |
| for standard inputs | |
|
— parameterizable — at "0" to "1", min. — at "0" to "1", max. |
0.2 ms, 0.4 ms, 0.8 ms, 1.6 ms, 3.2 ms, 6.4 ms and 12.8 ms, selectable in groups of four 0.2 ms 12.8 ms |
| for interrupt inputs | |
| — parameterizable | Yes |
| for technological functions | |
| — parameterizable |
Single phase: 3 @ 100 kHz & 3 @ 30 kHz, differential: 3 @ 80 kHz & 3 @ 30 kHz |
| Cable length | |
|
● shielded, max. ● unshielded, max. |
500 m; 50 m for technological functions 300 m; for technological functions: No |
| Digital outputs | |
|
Number of digital outputs ● of which high-speed outputs |
10 4; 100 kHz Pulse Train Output |
| Limitation of inductive shutdown voltage to | L+ (-48 V) |
| Switching capacity of the outputs | |
|
● with resistive load, max. ● on lamp load, max. |
0.5 A 5 W |
| Output voltage | |
|
● for signal "0", max. ● for signal "1", min. |
0.1 V; with 10 kOhm load 20 V |
| Output current | |
|
● for signal "1" rated value ● for signal "0" residual current, max. |
0.5 A 0.1 mA |
| Output delay with resistive load | |
|
● "0" to "1", max. ● "1" to "0", max. |
1 µs 5 µs |
| Switching frequency | |
| ● of the pulse outputs, with resistive load, max. | 100 kHz |
| Relay outputs | |
| ● Number of relay outputs | 0 |
| Cable length | |
|
● shielded, max. ● unshielded, max. |
500 m 150 m |
| Analog inputs | |
| Number of analog inputs | 2 |
| Input ranges | |
| ● Voltage | Yes |
| Input ranges (rated values), voltages | |
|
● 0 to +10 V — Input resistance (0 to 10 V) |
Yes ≥100k ohms |
| Cable length | |
| ● shielded, max. | 100 m; twisted and shielded |
| Analog outputs | |
| Number of analog outputs | 0 |
| Analog value generation for the inputs | |
| Integration and conversion time/resolution per channel | |
|
● Resolution with overrange (bit including sign), max. ● Integration time, parameterizable ● Conversion time (per channel) |
10 bit Yes 625 µs |
| Encoder | |
| Connectable encoders | |
| ● 2-wire sensor | Yes |
| 1. Interface | |
| Interface type | PROFINET |
| Isolated | Yes |
| automatic detection of transmission rate | Yes |
| Autonegotiation | Yes |
| Autocrossing | Yes |
| Interface types | |
|
● RJ 45 (Ethernet) ● Number of ports ● integrated switch |
Yes 1 No |
| Protocols | |
|
● PROFINET IO Controller ● PROFINET IO Device ● SIMATIC communication ● Open IE communication ● Web server ● Media redundancy |
Yes Yes Yes Yes; Optionally also encrypted Yes No |
| PROFINET IO Controller | |
| ● Transmission rate, max. | 100 Mbit/s |
| Services | |
|
— PG/OP communication — Isochronous mode — IRT — PROFIenergy |
Yes; encryption with TLS V1.3 pre-selected No No No |
|
— Prioritized startup — Number of IO devices with prioritized startup, max. — Number of connectable IO Devices, max. — Number of connectable IO Devices for RT, max. — of which in line, max. — Activation/deactivation of IO Devices — Number of IO Devices that can be simultaneously activated/deactivated, max. — Updating time |
Yes 16 16 16 16 Yes 8 The minimum value of the update time also depends on the communication component set for PROFINET IO, on the number of IO devices and the quantity of configured user data. |
| PROFINET IO Device | |
| Services | |
|
— PG/OP communication — Isochronous mode — IRT — PROFIenergy — Shared device — Number of IO Controllers with shared device, max. |
Yes; encryption with TLS V1.3 pre-selected No No Yes Yes 2 |
| Protocols | |
| Supports protocol for PROFINET IO | Yes |
| PROFIsafe | Yes |
| PROFIBUS | Yes; CM 1243-5 (master) or CM 1242-5 (slave) required |
| OPC UA | Yes; OPC UA Server |
| AS-Interface | Yes; CM 1243-2 required |
| Protocols (Ethernet) | |
|
● TCP/IP ● DHCP ● SNMP ● DCP ● LLDP |
Yes No Yes Yes Yes |
| Open IE communication | |
|
● TCP/IP — Data length, max. ● ISO-on-TCP (RFC1006) — Data length, max. ● UDP — Data length, max. |
Yes 8 kbyte Yes 8 kbyte Yes 1 472 byte |
| Web server | |
|
● supported ● User-defined websites |
Yes Yes |
| OPC UA | |
|
● Runtime license required ● OPC UA Server — Application authentication — User authentication — Number of sessions, max. — Number of subscriptions per session, max. — Sampling interval, min. — Publishing interval, min. — Number of server methods, max. — Number of monitored items, max. — Number of server interfaces, max. — Number of nodes for user-defined server interfaces, max. |
Yes; "Basic" license required Yes; data access (read, write, subscribe), method call, runtime license required Available security policies: None, Basic128Rsa15, Basic256Rsa15, Basic256Sha256 "anonymous" or by user name & password 10 50 100 ms 200 ms 20 1 000 2 2 000 |
| Further protocols | |
| ● MODBUS | Yes |
| communication functions / header | |
| S7 communication | |
|
● supported ● as server ● as client ● User data per job, max. |
Yes Yes Yes See online help (S7 communication, user data size) |
| Number of connections | |
| ● overall | PG Connections: 4 reserved / 4 max; HMI Connections: 12 reserved / 18 max; S7 Connections: 8 reserved / 14 max; Open User Connections: 8 reserved / 14 max; Web Connections: 2 reserved / 30 max; OPC UA Connections: 0 reserved / 10 max; Total Connections: 34 reserved / 64 max |
| Test commissioning functions | |
| Status/control | |
|
● Status/control variable ● Variables |
Yes inputs/outputs, bit memories, DBs, peripheral I/Os (without fail-safe), times, counters |
| Forcing | |
| ● Forcing | Yes; peripheral inputs/outputs (without fail-safe) |
| Diagnostic buffer | |
| ● present | Yes |
| Traces | |
|
● Number of configurable Traces ● Memory size per trace, max. |
2 512 kbyte |
| Interrupts/diagnostics/status information | |
| Diagnostics indication LED | |
|
● RUN/STOP LED ● ERROR LED ● MAINT LED |
Yes Yes Yes |
| Integrated Functions | |
|
Counter ● Number of counters ● Counting frequency, max. |
6 100 kHz |
| Frequency measurement | Yes |
| controlled positioning | Yes |
| Number of position-controlled positioning axes, max. | 8 |
| Number of positioning axes via pulse-direction interface | 4; With integrated outputs |
| PID controller | Yes |
| Number of alarm inputs | 4 |
| Number of pulse outputs | 4 |
| Limit frequency (pulse) | 100 kHz |
| Potential separation | |
| Potential separation digital inputs | |
|
● Potential separation digital inputs ● between the channels, in groups of |
No 1 |
| Potential separation digital outputs | |
|
● Potential separation digital outputs ● between the channels ● between the channels, in groups of |
Yes No 1 |
| EMC | |
| Interference immunity against discharge of static electricity | |
|
● Interference immunity against discharge of static electricity acc. to IEC 61000-4-2 — Test voltage at air discharge — Test voltage at contact discharge |
Yes 8 kV 6 kV |
| Interference immunity to cable-borne interference | |
|
● Interference immunity on supply lines acc. to IEC 61000-4-4 ● Interference immunity on signal cables acc. to IEC 61000-4-4 |
Yes Yes |
| Interference immunity against voltage surge | |
| ● Interference immunity on supply lines acc. to IEC 61000-4-5 | Yes |
| Interference immunity against conducted variable disturbance induced by high-frequency fields | |
| ● Interference immunity against high-frequency radiation acc. to IEC 61000-4-6 | Yes |
| Emission of radio interference acc. to EN 55 011 | |
|
● Limit class A, for use in industrial areas ● Limit class B, for use in residential areas |
Yes; Group 1 Yes; When appropriate measures are used to ensure compliance with the limits for Class B according to EN 55011 |
| Degree and class of protection | |
| IP degree of protection | IP20 |
| Standards, approvals, certificates | |
| CE mark | Yes |
| UL approval | Yes |
| cULus | Yes |
| FM approval | Yes |
| RCM (formerly C-TICK) | Yes |
| KC approval | Yes |
| Marine approval | Yes |
| Highest safety class achievable in safety mode | |
|
● Performance level according to ISO 13849-1 ● SIL acc. to IEC 61508 |
PLe SIL 3 |
| Ambient conditions | |
| Free fall | |
| ● Fall height, max. | 0.3 m; five times, in product package |
| Ambient temperature during operation | |
| ● min. | 0 °C |
| ● max. | 55 °C; Number of simultaneously activated inputs or outputs 4 or 3 (no adjacent points) at 60 °C horizontal or 50 °C vertical, 8 or 6 at 55 °C horizontal or 45 °C vertical |
| ● horizontal installation, min. | 0 °C |
| ● horizontal installation, max. | 55 °C |
| ● vertical installation, min. | 0 °C |
| ● vertical installation, max. | 45 °C |
| Ambient temperature during storage/transportation | |
|
● min. ● max. |
-40 °C 70 °C |
| Air pressure acc. to IEC 60068-2-13 | |
| ● Operation, min. | 795 hPa |
| ● Operation, max. | 1 080 hPa |
| ● Storage/transport, min. | 660 hPa |
| ● Storage/transport, max. | 1 080 hPa |
| Altitude during operation relating to sea level | |
|
● Installation altitude, min. ● Installation altitude, max. |
-1 000 m 5 000 m; Restrictions for installation altitudes > 2 000 m, see manual |
| Relative humidity | |
| ● Operation, max. | 95 %; no condensation |
| Vibrations | |
|
● Vibration resistance during operation acc. to IEC 60068-2-6 ● Operation, tested according to IEC 60068-2-6 |
2 g (m/s²) wall mounting, 1 g (m/s²) DIN rail Yes |
| Shock testing | |
| ● tested according to IEC 60068-2-27 | Yes; IEC 68, Part 2-27 half-sine: strength of the shock 15 g (peak value), duration 11 ms |
| Pollutant concentrations | |
| ● SO2 at RH < 60% without condensation | S02: < 0.5 ppm; H2S: < 0.1 ppm; RH < 60% condensation-free |
| configuration / header | |
| configuration / programming / header | |
| Programming language | |
|
— LAD — FBD |
Yes; incl. failsafe Yes; incl. failsafe |
|
|
Yes |
| Know-how protection | |
|
● User program protection/password protection ● Copy protection ● Block protection |
Yes Yes Yes |
| Access protection | |
|
● protection of confidential configuration data ● Protection level: Write protection ● Protection level: Read/write protection ● Protection level: Complete protection |
Yes Yes Yes Yes |
| programming / cycle time monitoring / header | |
| ● cycle monitoring time / adjustable | Yes |
| Dimensions | |
| Width | 130 mm |
| Height | 100 mm |
| Depth | 75 mm |
| Weights | |
| Weight, approx. | 585 g |
| 6ES7214-1AF40-0XB0 | 6ES7212-1AE40-0XB0 | 6ES7214-1HF40-0XB0 |
| 6ES7212-1HF40-0XB0 | 6ES7212-1AF40-0XB0 | 6ES7215-1HF40-0XB0 |
| 6ES7215-1AF40-0XB0 | 6ES7211-1HE40-0XB0 | 6ES7212-1BE40-0XB0 |
| 6ES7212-1HE40-0XB0 | 6ES7211-1BE40-0XB0 | 6ES7211-1AE40-0XB0 |
| 6ES7212-1HF42-4YB1 | 6ES7217-1AG40-0XB0 | 6ES7215-1HG40-0XB0 |
| 6ES7215-1AG40-0XB0 | 6ES7214-1BG40-0XB0 | 6ES7214-1HG40-0XB0 |
| 6ES7212-1HF41-4YB1 | 6ES7214-1AG40-0XB0 | 6ES7215-1BG40-0XB0 |